Comparative Study of Split Air Conditioner Performance on Pipe Length Variations in R32, R410A, and R290 Refrigerants

Authors

  • Imam Nursyahied Universitas Negeri Jakarta
  • Thaha Ismail Jayadinata Universitas Negeri Jakarta
  • Alynda Natasya Putri Ardianto Universitas Negeri Jakarta
  • Aris Sunawar Universitas Negeri Jakarta
  • Readysal Monantun Universitas Negeri Jakarta

DOI:

https://doi.org/10.21009/JKEM.11.2.8

Keywords:

cooling capacity, pressure drop, EER, thermodynamic, HVAC

Abstract

Split air conditioners are one of the most commonly used air conditioning systems due to their compact design and flexible installation. The system consists of two units connected by copper pipes as a refrigerant circulation line. This study presents a comparative analysis of the thermodynamic performance of split AC on pipe length variations using three refrigerants, R32, R410A, and R290, with a simulation approach based on CoolProp v6.4 and REFPROP v10.0 software. The length variations of the tested pipes are 15, 20, 25, and 30 m with operating conditions according to ISO 5151:2017 standards. The parameters evaluated included cooling capacity (Qe), input power (Pinput), energy efficiency ratio (EER), and pressure drop (Δp). The accuracy of both software is measured using MAPE and RMSE metrics against manual calculations as a reference. The simulation results showed that the increase in pipe length led to an average decrease in Qe of 10.3-10.4% from the 15 m to 30 m pipe length in all three refrigerants. R290 recorded the highest EER (3.87-3.48), followed by R32 (3.72-3.33), and R410A (3.36-3.01). R410A produces the largest pressure drop (25.87 kPa at 30 m), while R290 has the lowest pressure drop (12.56 kPa). Accuracy analysis showed that REFPROP was more accurate than CoolProp on all parameters with an average MAPE difference of 0.57%, although the difference between the two was relatively small. Large deviations in the Δp parameter (>168%) are due to fundamental flow model differences, not thermodynamic errors. The results of this study provide a scientific reference in the selection of the optimal refrigerant and simulation software for split air conditioning installations with varying pipe lengths.

References

[1] S. Benyahia, “Every action count: kigali amendment,” United Nations Environment Programme (UNEP), 2022.

[2] C. M-. Royo, A. M-. Babiloni, J. N-. Esbrí, and Á. B-. Cervera, “Comparative analysis of HFO-1234ze(E) and R-515B as low GWP alternatives to HFC-134a in moderately high temperature heat pumps,” International Journal of Refrigeration, vol. 124, pp. 197-206, 2021, doi: 10.1016/j.ijrefrig.2020.12.023.

[3] P. Purohit, T. Chao, R. Cooke, H. Dhont, R. Kaur, R. Peixoto, H. W-. Terrinoni, and A. Woodcock, “The importance of lifecycle refrigerant management in climate and ozone protection,” Sustainability, vol. 17, no. 1, p. 53, 2025, doi: 10.3390/su17010053.

[4] ISO 5151:2017/Amd 1:2020, “Non-ducted air conditioners and heat pumps — Testing and rating for performance,” https://www.iso.org/standard/80279.html, 2020 (accessed 1 June 2026).

[5] I. H. Bell, J. Wronski, S. Quoilin, and V. Lemort, “Pure and pseudo-pure fluid thermophysical property evaluation and the open-source thermophysical property library coolprop,” Industrial & Engineering Chemistry Research, vol. 53, no. 6, pp. 2498-2508, 2014, doi: 10.1021/ie4033999.

[6] E. W. Lemmon, M. L. Huber, and M. O. McLinden, “NIST Reference Fluid Thermodynamic and Transport Properties REFPROP,” https://www.nist.gov/system/files/documents/srd/REFPROP8_manua3.htm, 2007 (accessed 1 June 2026).

[7] K. Sumeru, T. P. Pramudantoro, A. Setyawan, R. Muliawan, T. Tohir, and M. F. B. Sukri, “Effect of compressor discharge cooler heat exchanger length using condensate water on the performance of a split type air conditioner using R32 as working fluid,” Energies, vol. 15, no. 21, p. 8024, 2022, doi: 10.3390/en15218024.

[8] T. N. Aynur, “Variable refrigerant flow systems: A review,” Energy and Buildings, vol. 42, no. 7, pp. 1106-1112, 2010, doi: 10.1016/j.enbuild.2010.01.024.

[9] B. Lei, C. Wang, M. Noro, Q. Wu, and J. Wu, “Experimental study on startup characteristics of R290 air conditioner with low lubricant charge,” International Journal of Refrigeration, vol. 153, pp. 1-9, 2023, doi: 10.1016/j.ijrefrig.2023.06.015.

[10] A. Setyawan, W. H. Mitrakusuma, and H. Najmudin, “Performance of a split air conditioner under different refrigerant pipe length,” in AIP Conference Proceedings, vol. 2720, p. 040034, 2023, doi: 10.1063/5.0136936.

[11] J. Zhang, H. Zeng, D. D. Djapa, and B. K. Rugwizangoga, “Physical property calculation and refrigeration cycle analysis of mixed refrigerant R32/R290,” Buildings, vol. 15, no. 7, p. 1071, 2025, doi: 10.3390/buildings15071071.

[12] M. Z. Saeed, L. Contiero, S. Blust, Y. Allouche, A. Hafner, and T. M. Eikevik, “Ultra-low-temperature refrigeration systems: a review and performance comparison of refrigerants and configurations,” Energies, vol. 16, no. 21, p. 7274, 2023, doi: 10.3390/en16217274.

[13] I. H. Bell, “Mixture models for refrigerants R-1234yf/134a, R-1234yf/1234ze(E), and R-134a/1234ze(E) and interim models for R-125/1234yf, R-1234ze(E)/227ea, and R-1234yf/152a,” Journal of Physical and Chemical Reference Data, vol. 51, no. 1, p. 013103, 2022, doi: 10.1063/5.0086060.

[14] M. L. Huber, E. W. Lemmon, I. H. Bell, and M. O. McLinden, “The NIST REFPROP database for highly accurate properties of industrially important fluids,” Industrial & Engineering Chemistry Research, vol. 61, no. 42, pp. 15449−15472, 2022, doi: 10.1021/acs.iecr.2c01427.

[15] R. R. Setiawan, H. Ambarita, T. B. Sitorus, H. V. Sihombing, and R. H. Malau, “Experimental study and performance analysis of direct coupled solar vapor compression refrigeration system,” in Journal of Physics: Conference Series, vol. 2942, p. 012028, 2025. doi: 10.1088/1742-6596/2942/1/012028.

[16] J. M. Kim and S. H. Nam, “IEQ and energy effect analysis according to empirical full energy efficiency retrofit in south korea,” Energy and Buildings, vol. 235, p. 110629, 2021, doi: 10.1016/j.enbuild.2020.110629.

[17] Y. Zhao and L. K. Foong, “Predicting electrical power output of combined cycle power plants using a novel artificial neural network optimized by electrostatic discharge algorithm,” Measurement, vol. 198, p. 111405, 2022, doi: 10.1016/j.measurement.2022.111405.

[18] M. J. Díaz, I. Caro, and R. Martín, “Transforming experimental teaching of fluid mechanics and heat transfer courses due to the COVID-19 pandemic,” Education Science, vol. 13, no. 7, p. 650, 2023, doi: 10.3390/educsci13070650.

[19] D. Chicco, M. J. Warrens, and G. Jurman, “The coefficient of determination r-squared is more informative than SMAPE, MAE, MAPE, MSE and RMSE in regression analysis evaluation,” PeerJ Computer Science, vol. 7, p. e623, 2021, doi: 10.7717/peerj-cs.623.

[20] Z. Zhang, L. Shi, G. He, J. Hua, D. Cai, and Y. Liu, “Experimental analysis on flow boiling heat transfer of R490A: a new hydrocarbon blend for low-GWP refrigeration,” International Communications in Heat and Mass Transfer, vol. 169, p. 109917, 2025, doi: 10.1016/j.icheatmasstransfer.2025.109917.

[21] J. N-. Esbrí and A. M-. Babiloni, “Experimental analysis of a high temperature heat pump prototype with low global warming potential refrigerant R-1336mzz(Z) for heating production above 155 °C,” International Journal of Thermofluids, vol. 17, p. 100304, 2023, doi: 10.1016/j.ijft.2023.100304.

Downloads

Published

2026-07-31

How to Cite

[1]
I. . Nursyahied, T. I. Jayadinata, A. N. P. Ardianto, A. Sunawar, and R. Monantun, “Comparative Study of Split Air Conditioner Performance on Pipe Length Variations in R32, R410A, and R290 Refrigerants”, J. Konv. Ener. Manuf. , vol. 11, no. 2, pp. 182 – 192, Jul. 2026.

Issue

Section

Articles